    OBJECTIVE

    The objective is to monitor the critical alarms. A small mimic panel installed outside MER room for visual indication of any troubles / faults. The EMS system shall be capable to provide alarm outputs to be connected to the SST security system with auto-dialing & SMS functionality for local alarms. The system shall allow interfacing connections (dry contact signals to be connected to the security rack) with SST Sydney control room through security network to allow detailed monitoring from Sydney.

    SYSTEM DESCRIPTION

    T+Rh sensors to be installed in the MER, SER, UPS & Battery room and should be displayed on the mimic panel. The panel should have the graphical representation of MER, SER, UPS & Battery room layouts and the following alarms will be integrated on the mimic panel.
    All power dependent alarms shall be extended after 60 seconds time delay.
    UPS room
    • Normal power failure alarm
    • Essential power ON alarm
    • Server room UPS common alarm
    • Workstation UPS common alarm
    • UPS room high temperature alarm
    • UPS room high humidity alarm
    • UPS room HSSD activation common alarm
    • UPS room water leakage alarm
    • Any fire common alarm
    • UPS room Novec 1230 activation alarm
    • UPS room A/C common alarm
    • Panel System Status like Buzzer / Reset / Mute / System Test / Mimic Self Battery Alarm should also form a part of the Mimic Panel.
    Battery room
    • Battery room water leakage alarm
    • Any fire common alarm
    • Battery room high temperature alarm
    • Battery room high humidity alarm
    • Battery room Novec 1230 activation alarm
    • Battery room A/C common alarm
    MER room
    • MER room high temperature alarm
    • MER room high humidity alarm
    • MER room PAC / CRAC common alarm
    • MER room HSSD activation common alarm
    • MER room water leakage alarm
    • Any fire common alarm
    • MER room Novec 1230 activation alarm
    SER room
    • SER room high temperature alarm
    • SER room high humidity alarm
    • SER room A/C common alarm
    • SER room water leakage alarm
    • Any fire common alarm
    • SER room Novec 1230 activation alarm
    • SER Workstation UPS common alarm